EnergyCell RE Front Terminal Battery |
| EnergyCell 170RE |
EnergyCell 200RE |
Cells Per Unit: |
6 |
6 |
Voltage Per Unit: |
12 Vdc |
12 Vdc |
Operating Temperature Range: |
Discharge: -40°F (-40°C) to +160°F (71°C) Charge: -10°F (-23°C) to +140°F (60°C) |
Optimal Operating Temperature Range: |
+74°F (23°C) to +80°F (27°C) |
Recommended Maximum Charging Current Limit per String: |
25 Adc |
30 Adc |
Float Voltage Charge: |
13.62 to 13.8 Vdc/unit Average at 77°F (25°C) |
Equalization and Cycle Service Charging Limits: |
14.4 to 14.8 Vdc/unit Average at 77°F (25°C) |
Self Discharge: |
Battery can be stored up to 6 months at 77°F (25°C) before a freshening
charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than
batteries stored at lower temperatures. |
Temperature Compensation Factor (Charging): |
5mV per degree C per cell (2V) |
Terminal: |
Threaded copper alloy insert terminal to accept ¼-20 UNC bolt |
Terminal Hardware Initial Torque: |
110 in-lbs (12.4 Nm) |
Weight (lbs/kg): |
115 lbs (52 kg) |
131 lbs (60 kg) |
Dimensions: |
11.14 x 22.01 x 4.95” (28.3 x 55.9 x 12.6 cm) |
12.60 x 22.01 x 4.95” (32.0 x 55.09 x 12.6 cm) |