Square D > 30 Amp 600 VAC/VDC Disconnect, Safety Switch, 3 Pole - NEMA 3R
For Square D safety switches, the "N" in NRB stands for Neutral.
NRB = Isolated terminal block equipped switch. For Square D RB models = No terminal block.
Manufacturer Part Number: H361RB
Phase
|
Three Phase
|
Number of Poles
|
3
|
Maximum Current Rating
|
30 Amps
|
NEMA Class
|
3R Rainproof
|
Maximum Horse Power Rating
|
- 5 hp 480 V at AC 50-60 Hz for 3 phase conforming to NEC 240.6
- 15 hp 480 V at AC 50-60 Hz for 3 phase conforming to NEC 430.52
- 7.5 hp 600 V at AC 50-60 Hz for 3 phase conforming to NEC 240.6
- 20 hp 600 V at AC 50-60 Hz for 3 phase conforming to NEC 430.52
- 5 hp 250 V at DC
- 15 hp 600 V at DC
|
Maximum Power
|
20 HP
|
Electrical Connection
|
Lugs
|
Weight
|
9.11 lbs. / 4.13 kg
|
Dimensions
|
7.55" W x 14.88" H x 4.86" D
|
For inverters that do not include a DC disconnect, or when an additional DC disconnect is required, one of these 600 VDC disconnects can be used. Many utilities require an AC disconnect between a grid-tie inverter and the AC load center, close to the AC service entrance, and with a visible and lockable handle.
The Square-D 600 VDC-rated 30 A, 60 A, and 100 A three-pole safety switches are rated by Square-D to handle one 600 VDC circuit per pole for PV (although they are not UL-listed for this purpose). The 30 A switch is rated for 16 A short-circuit current (Isc at PV module STC) for non-fused versions, and 12.8 A (Isc) for fused versions. The 60 A switch is rated for 48 A (Isc) for non-fused versions and 38 A (Isc) for fused versions. The 100 A switch is rated for 80 A (Isc) for non-fused versions and 64 A (Isc) for fused versions.
All of the Square-D 600 VDC non-fused disconnects are rated for disconnecting one circuit at full rated current using two poles in series. Fused disconnects are rated for 80% of switch current rating at up to 600 VDC.
Use Class-R fuses of the proper voltage and amperage for fused disconnects. 600 V fuses will not fit into 240 VDC disconnects, and 250 VAC/125 VDC fuses will not fit into 600 V disconnects, and vice-versa.
Heavy duty UL-listed safety disconnect switches are offered fusible and non-fusible, NEMA 1 indoor rated or NEMA 3R outdoor rated, with external lockable handle and door. Service disconnect for AC or DC systems rated to 600 volts. 3R switches accept top bolt-on hubs.